• Stone Wool

Pipe Section

  • Pre-formed pipe section
  • Rigid
  • Ease of installation
  • Less joints and wastage
  • Good compressive strength
  • No sagging

Range

  • Density : 100 to 160 kg/m3
  • Thickness : 25 to 100 mm
  • Diameter : 15 to 600 mm (NB)
  • Length : 1.2 to 1.25 m

Facings

  • Unfaced / plain
  • Aluminium : FSK

Basic Information

Make / Brand Rockinsul
Material Stone wool pipe section
Standard / Code IS 9842, ASTM C 547

Product Performing Criteria

Parameter Values Standards
Thermal Conductivity
(W/m.K)
0.065 at 200oC mean temperature IS 9842 / ASTM C 547
Thermal Resistance
(m2 K/W)
Calculated as per thickness and thermal conductivity of insulation

General Material Properties

Parameter Values Standards
Non-combustibility Non-combustible / Incombustible BS 476 Part 4, IS 9842
Surface Burning Characteristics : Flame Spread Index ≤ 25 ASTM E84
Surface Burning Characteristics : Smoke Developed Index ≤ 50 ASTM E84
Water Vapour Sorption Less than 5% by volume ASTM C1104, ASTM C1104M, BS 2972
Water Absorption
(kg/m2)
Less than 0.5 BS 2972 Part 11
Shot content < 25% IS 9842
Sulphur / Chloride Chloride : less than 20 ppm
Sulphur content : less than 0.2%
IS 9842
Mold growth No fungal growth IS 9842
Alkalinity 7 to 10 IS 9842

Certifications and Approvals

Environment Health Safety